Guide · NOM-002-STPS

NOM-002-STPS: ordinary or high fire risk, and what each one requires

A guide based on the official text to classifying your plant's fire risk and knowing what an inspector will ask for in each case.

Updated 6 min readCSE Industrial technical team

In short

  • NOM-002-STPS-2010 requires every workplace to classify its fire risk, as a whole or by area, as ordinary or high.
  • It is high if the built area is 3,000 m² or more, if there are pyrophoric or explosive materials in any quantity, or if the inventories of flammables and combustibles, each divided by its threshold, add up to 1.
  • Every workplace needs a plan showing routes and equipment, safety instructions, a fire emergency plan, yearly training, and extinguishers inspected monthly and serviced at least once a year.
  • High risk adds fire brigades, two drills a year instead of one, fixed systems and alarms, more extinguishers and a document proving compliance.
Contents

What is NOM-002-STPS-2010?

NOM-002-STPS-2010, Safety conditions – Fire prevention and protection in workplaces, sets the requirements for preventing fires and protecting workers if one breaks out. Mexico's labor ministry (STPS) published it in the Official Gazette (DOF) on December 9, 2010; it took effect six months later, replaced NOM-002-STPS-2000 and applies to every workplace in Mexico.

Its starting point is the fire-risk classification: almost every obligation changes depending on whether the workplace, or each of its areas, is ordinary or high risk.

How to classify fire risk

Classification uses Table A.1 in Appendix A, looking at the built area and the maximum inventory recorded in a year for each type of material:

Fire-risk determination (Table A.1)
ItemOrdinary riskHigh risk
Built areaUnder 3,000 m²3,000 m² or more
Flammable gasesUnder 3,000 L3,000 L or more
Flammable liquidsUnder 1,400 L1,400 L or more
Combustible liquidsUnder 2,000 L2,000 L or more
Combustible solids, including furnitureUnder 15,000 kg15,000 kg or more
Pyrophoric and explosive materialsNot applicableAny quantity

With several materials, checking each row on its own isn't enough: the standard adds up each inventory as a share of its threshold (A.1.3). If (flammable gases ÷ 3,000 L) + (flammable liquids ÷ 1,400 L) + (combustible liquids ÷ 2,000 L) + (combustible solids ÷ 15,000 kg) comes to 1 or more, the risk is high. For office furniture you may assume an average of 60 kg per worker.

Many industrial buildings exceed 3,000 m² of built area, which on its own makes their risk high (A.1.4). Classification may be done by area when areas are separated by fire-resistant construction or by enough distance to prevent rapid spread; it must be redone when maximum inventories change, and it is documented in writing with the area, inventories, calculation and the name of the person responsible (A.1.2, A.1.6 and A.2).

Obligations for every workplace

  • Classify the fire risk, as a whole or by area (5.1).
  • Post an up-to-date sketch or plan showing risk areas, detection devices, firefighting equipment, evacuation routes, exits and safe places (5.2).
  • Have safety instructions for each area, including hot work, and share them with workers, contractors and visitors (5.3 and 7.1).
  • Have a fire emergency response plan (5.5 and chapter 8).
  • Run fire emergency drills at least once a year (5.7).
  • Train workers under a yearly theory-and-practice program (5.8).
  • Have detection devices and firefighting equipment suited to the classes of fire that may occur (5.10).
  • Follow yearly inspection programs for firefighting equipment, electrical installations and, where present, gas installations, with recorded results (7.4 to 7.7).

What high fire risk adds

  • Fire brigades, trained and with their personal protective equipment (5.6 and 5.9).
  • Two drills a year, at a minimum (5.7).
  • Fixed fire-protection systems and fire alarms, in addition to detection devices and extinguishers (5.10).
  • More extinguishers: one per 200 m² instead of one per 300 m² (7.17).
  • An extended emergency plan that includes drill results and the most serious foreseeable accidents (8.2).
  • A document proving compliance: an STPS verification record under the Occupational Safety and Health Self-Management Program, a compliance opinion from an accredited and approved verification unit, or a record from the local civil-protection authority (5.11).

Extinguishers: how many, where and how often

Fire extinguishers (section 7.17)
RequirementOrdinary riskHigh risk
Minimum number1 per 300 m² or fraction1 per 200 m² or fraction
Maximum travel distance, class A, C or D fires23 m23 m
Maximum travel distance, class B fires15 m10 m (15 m for wheeled units)
Maximum travel distance, class K fires10 m10 m

They are mounted no higher than 1.50 m from the floor to their top, protected from damage, signposted and unobstructed. With automatic suppression systems the required number may be cut by up to half, provided each extinguisher holds at least 6 kg or 9 L (7.17).

Inspection is monthly, under a yearly program with recorded results: location, access, seal or tamper tag, pressure in the green zone, damage and a current label (7.2 and 7.3). Servicing happens at least once a year, guaranteed under NOM-154-SCFI, and an extinguisher taken away for service is replaced in the same spot by one of at least the same type and capacity (7.18).

Drills: planning and records

Drills may cover individual areas or the whole workplace (10.1). Their planning must be in writing, with the people coordinating them, the date and time, the scope, the most critical emergency scenarios, the sequence of actions and, where applicable, the participation of local emergency services (10.2).

Their results are recorded with the workplace and areas involved, the number of participants, the resources used, the deviations detected, recommendations for updating the emergency plan, the duration and the coordinators' names (10.3).

What happens if you don't comply?

Mexico's Federal Labor Law sets fines of 250 to 5,000 times the UMA (Mexico's daily reference unit) for employers who don't follow safety and hygiene standards in their facilities (article 994, section V). Beyond the fine, the standard exists so that a small fire doesn't end in injuries or a plant shutdown.

How we help

We classify your plant's fire risk, check your program against the standard's requirements, organize your extinguisher, drill and training records and leave the evidence ready for the inspection, at plants in Tijuana, Mexicali, Ensenada and Tecate. See our fire protection service or request an assessment.

Frequently asked questions

It is if its built area is 3,000 m² or more, if it handles pyrophoric or explosive materials in any quantity, or if its inventories of flammable gases, flammable liquids, combustible liquids and combustible solids, each divided by its threshold, add up to 1 or more.

At least one per 300 m² at ordinary risk or one per 200 m² at high risk, without exceeding the maximum travel distances for each class of fire.

At least once a year at ordinary risk and twice a year at high risk, with written planning and recorded results.

They are inspected monthly, with recorded results, and serviced at least once a year.

No. They are separate obligations, one under labor law and one under civil protection, and they complement each other. For high-risk workplaces, the standard accepts a record from the local civil-protection authority as one of the documents that prove compliance.

Official sources

This guide summarizes the official text in force on the update date and is for information only. It doesn't replace reading the regulation or an assessment of your case; if anything differs, the official published text prevails.

Related service

Fire protection: NOM-002-STPS consulting

Risk grade determined, complete program and documented drills — no surprises at inspection.

See the service

Let's talk about your next audit.

Tell us about your case. Within 24–48h you'll receive a written scope with deliverables, timeline, and pricing — no commitment.

WhatsApp

If you're not sure which service fits, we quote the minimum viable scope.